Print Page



Description

Power factor controllers RMB 10

Manufactured in 6 and 12-outputs versions. Available at request are fast version controlling capacitor thyristor comutators, HV version and version with RS-485 or RS-232 interface.

  • Dimensions: 144×144×75mm (MAXI)
  • Type: front pannel mounted

Technical data

Power Factor Controller Type: RPC-10
Supply power range Us=230 V (+10%, -15%), 50 / 60 Hz, max. 6VA
Acceptable measuring voltage Up=5...500 V, 50 / 60Hz,
Nominal measuring current In = 5 A
Power consumption of current circuit max 0,5 VA
Measuring current range 0.01... 1.2 In continuous
Power factor setting range 0.5ind .. 1,0 .. 0,5cap (step 0,01)
Setting range of insensitivity zone (c/k) 0.03...1,0 (step 0,01 )
Switching time between steps
(separatly Time ON and Time OFF)
standard 2...240s (step 1 second)
option type: HV 0 .. 1200second
option type: FAST for thyristor comutators 0,04 .. 9,9s (step 0,01 second)
Safety time setting before reconnection typical setting 40s (0 .. 99 s in steps of every 1s)
option type: HV 0 .. 1200second
Number of outputs 6 or 12
Output contacts rating 4A , 250 V , 1000VA
Alarm contact 4A , 250 V , 1000VA
Indication of the active outputs LED diodes
Programming facilities four-pushbutton keypad
Number of switching codes 16 (sequentions outs)
Harmonic distortion presentation voltage: up to 15th
current: up to 15th
Interface (option on request) RS-485 or RS-232
Protection degree IP54 (front); IP20 (rear)
Ambient temperature range -15°C .. 60°C
Outer dimensions (W x H x D) 144 × 144 × 75 mm
Weight ca. 1kg

Schemat

Przykładowy schemat regulacji poziomu w zbiorniku