Description
Power factor controllers RMB 10L
12 output version of controller, in hausing designed to be mounted to 35mm rail. All parameters of RMB-10 controller at low price.
- Dimensions: 106×90×58mm (MINI 12)
- Type: 35mm bus mounted
Technical data
| Power Factor Controller | Type: RPC-10L |
| Supply power range | Us=230 V (+10%, -15%), 50 / 60 Hz, max. 4VA |
| Acceptable measuring voltage | Up=5...500 V, 50 / 60Hz, |
| Nominal measuring current | In = 5 A |
| Power consumption of current circuit | max 0,5 VA |
| Measuring current range | 0.01... 1.2 In continuous |
| Power factor setting range | 0.5ind .. 1,0 .. 0,5cap (step 0,01) |
| Setting range of insensitivity zone (c/k) | 0.03...1,0 (step 0,01 ) |
| Switching time between steps (separatly Time ON and Time OFF) |
standard 2...240s (step 1 second) |
| Safety time setting before reconnection | typical setting 40s (0 .. 99 s in steps
of every 1s) |
| Number of outputs | 12 |
| Output contacts rating | 2A , 250 V , 500VA |
| Alarm contact | - |
| Indication of the active outputs | LED diodes |
| Programming facilities | four-pushbutton keypad |
| Number of switching codes | 16 (sequentions outs) |
| Harmonic distortion presentation | voltage: up to 15th current: up to 15th |
| Interface (option on request) | RS-485 or RS-232 |
| Protection degree | IP54 (front); IP20 (rear) |
| Ambient temperature range | -15°C .. 60°C |
| Outer dimensions (W x H x D) | 106 × 90 × 58 mm |
| Weight | ca. 0,6kg |
Schemat