Technical data

Power Factor Controller Type: RPC-10L
Supply power range Us=230 V (+10%, -15%), 50 / 60 Hz, max. 4VA
Acceptable measuring voltage Up=5...500 V, 50 / 60Hz,
Nominal measuring current In = 5 A
Power consumption of current circuit max 0,5 VA
Measuring current range 0.01... 1.2 In continuous
Power factor setting range 0.5ind .. 1,0 .. 0,5cap (step 0,01)
Setting range of insensitivity zone (c/k) 0.03...1,0 (step 0,01 )
Switching time between steps
(separatly Time ON and Time OFF)
standard 2...240s (step 1 second)
Safety time setting before reconnection typical setting 40s (0 .. 99 s in steps of every 1s)
Number of outputs 12
Output contacts rating 2A , 250 V , 500VA
Alarm contact -
Indication of the active outputs LED diodes
Programming facilities four-pushbutton keypad
Number of switching codes 16 (sequentions outs)
Harmonic distortion presentation voltage: up to 15th
current: up to 15th
Interface (option on request) RS-485 or RS-232
Protection degree IP54 (front); IP20 (rear)
Ambient temperature range -15°C .. 60°C
Outer dimensions (W x H x D) 106 × 90 × 58 mm
Weight ca. 0,6kg